位置:7580942 > 7580942详情

7580942中文资料

厂家型号

7580942

文件大小

257.68Kbytes

页面数量

4

功能描述

Frequency Transducer/Pulse Counter 2-channel

数据手册

下载地址一下载地址二到原厂下载

简称

TURCK图尔克

生产厂商

Turck, Inc.

中文名称

德国图尔克集团公司官网

7580942数据手册规格书PDF详情

The frequency transducer/pulse counter

IMX12-FI01-2SF-2I-C0/24VDC is equipped

with intrinsically safe input circuits and transmits frequency signals up to 20000 Hz electrically isolated from the Ex to the non-Ex area.

In addition, the input signals can be monitored

for slip. The devices are suitable for operation

in zone 2.

Each channel of the 2-channel device is

equipped with an intrinsically safe input for

connection of sensors acc. to EN 60947-5-6

(NAMUR) or potential-free contacts. On the

output side, a current output 0/4 … 20 mA is

available for each channel.

The device is parameterized via FDT and

IODD with a PC. The current output can be

set to 0/4…20 mA (source or sink optional). In

accordance with the parameterization (E1, E2,

E1-E2 or E2-E1), the input signals are provided as a 0/4…20 mA standard current signal.

The devices have a green power LED (Pwr)

and a red LED to indicate internal faults. For

each input circuit there is a yellow and a red

status LED. A fault in the input circuit leads

to a flashing red LED according to NE44, an

internal fault to a steady read LED. The fault

current can be adjusted to 21.5

mA.

The device can be used in safety circuits up

to SIL2 (high and low demand according to

IEC 61508) and meets the requirements of

the NE21. It is equipped with removable screw

terminals.

The device is equipped with removable screw

terminals.

■ Input circuits monitored for wire-break and

short-circuit

■ Parameterized via PC

■ Complete galvanic isolation

■ Input reverse-polarity protected

■ Output circuits monitored for wire break

and short circuit

■ ATEX, IECEx, cFM, cUL, NEPSI, INMETRO, KOSHA, TR CU EAC CMI, TIIS,

■ Installation in zone 2

■ SIL 2

7580942 芯片相关型号