位置:S200-D > S200-D详情

S200-D中文资料

厂家型号

S200-D

文件大小

1328.32Kbytes

页面数量

35

功能描述

Miniature circuit-breakers S 200/S 200 M Residual-current-operated circuit-breakers F 200 Cross wiring/accessories

数据手册

下载地址一下载地址二

生产厂商

ABB

S200-D数据手册规格书PDF详情

Outstanding features Applications

 All round protection against contact with live parts in acordance with

DIN VDE 106 part 100.

 Due to new design: Upper and lower shoulders reduced.

More working space between component rows.

Outgoing and incoming connection points easily accessible.

 New, failsafe, bi-directional cylinder lift terminal, ensuring a faster, totally

error-free connection.

As you tighten the screw, the terminal draws together to simultaneously

close the front and rear wiring inputs.

5

 New quick-fastening technique for easy disconnection of the device

from the assembly.

No time-consuming extra work:

Cross-wiring remains with the assembly.

To remove the device, just loosen the screw, lift the device and pull it

out.

If neccessary, all devices of the series connected to the new

pro M compact cross-wiring rails may be exchanged easily and quickly,

e.g. to implement the adaptation to the VDE standard

0100 part 410.

Easy to add on MCB for extensions.

 New, integrated auxiliary contact, factory fitted, reduces space by 50 %.

Cross wiring to customary compact busbar possible.

 Self-adhesive identification labels are provided for all devices, ensuring

clear and accurate identification.

Every detail of System pro M compact has now been optimised to meet the

user’s requirements.

Fuirthermore, System pro M compact offers you many different ways to

label the switchgear cabinet and built-in consumer unit in a professional

manner.

Individual, effecient labeling of devices.

 Pad lock prevents unauthorized switching to ON or OFF.

 Complete range of tripping characteristics in B, C, D, K, Z.

 High rated switching capacity of 6 000 A (S 200) or 10 000 A (S 200 M).

 Current limitation is below the values prescribed by the VDE, therefore

higher selectivity rating than energy limitation class 3.

 Disconnector abilities according to DIN VDE 0660 part 107, surge withstand

capability 6 kV (1.2/50).

This creates a strong, contactassured connection between the wires and

the device, in a single operation.

Busbar is installed at the back terminals (A). Connection of conductors

on the front terminals (B).

Result: a clear view on all connection points.

Never fumble for the right connection point again.

Substantially improved cross-wiring safety.

Tangible time-savings.

 Connection possible for single, multi and finely stranded conductors

of 0.75 to 25 mm2.

It is also possible to connect conductors with different cross section at

the same time.

 New cross wiring busbars.

Standard length sizes or meter length cutable.

Description

The MCBs of the S 200/S 200 M series have a current-

limiting effect. They have two different trip releases

acting on the contact mechanism

1. the delayed thermal release providing overload

protection

2. the electromagnetic instantaneous release with

“hammer trip” solenoid providing fault current

protection.

They offer:  high short-circuit capacity

 high selectivity for back-up fuse

 In case of short-circuit, low stress

on the cable in the point of fault due

to the high limitation of the let-through

ƒi2dt (current heating value).